Application: |
- Airport & Public Facility Security and Safety
- Loss Prevention
- Restrict the egress of patients for safety
|
Operation: |
- Typically used on exit doors when unauthorized egress is initiated when in the locked mode
- The person exiting must wait the specified 15 or 30 seconds where available
- The door unlocks after 15 seconds permitting egress
|
Note: |
- One (1) wall controller is required for the 4501/4601 Delayed Egress Exit Device
- Requires 3902 Mortise Cylinder, sold separately
(Conventional Core Only, 1-1/8" length recommended) |
Delayed Egress
Wall Mount Controller
Delayed Egress
Features: |
- 15 or 30 second egress delay
- 1 or 2 second nuisance delay
- Built-in function keypad provides alarm and lock reset, 1 to 30 second bypass, sustained bypass, and additional keyswitch
- Control inputs include 1 to 30 second request to exit and access bypass with anti-tailgate and alarm rest
- Field selectable automatic or manual power up after emergency release or power loss
|
Built-in annunciation: |
- Armed mode
- Nuisance mode
- Irreversible egress mode
- Release mode
- Digital countdown display
- Field selectable voice notification or tone
- Field selectable male voice with security message or female voice with safety message
|
Code Complaince: |
- FC International
- IBC International Building Code
- NFPA 101 Life Safety Code
- NFPA 1 Uniform Fire Code
- California Building Code
|
Voltage Input: |
- Auto Sensing 12/24VDC
|
Reset Input: |
- N/O, Dry input
|
REX Input: |
- N/O, Dry input
|
Trigger: |
- N/C or N/O, Dry input
|
Monitoring Outputs: |
- Alarm output - 1 amp @ 30VDC SPDT, Dry
- Locked output - 1 amp @30VDC SPDT, Dry
|
Controller Dimensions: |
- 6-1/2" x 4-1/2" x 1-1/2" (165 x 114 x 38 mm)
|
Accessories: |
- 2-679-0641 3-Gang interior surface mount box
- 2-679-0642 Shroud for surface mount box
|
Finishes: |
- ALM
|
Description | File Number |